The AS-Interface can be integrated into the process control system as follows using the AS-Interface block library for SIMATIC PCS 7:
AS?i integration in SIMATIC PCS 7 via PROFIBUS DP AS?i integration in SIMATIC PCS 7 via PROFINET IO The AS interface operates according to the master/slave principle. The AS-i master module (DP/AS?i LINK Advanced, CP 343?2, CP 343?2P, CM AS?i Master ST or IE/AS?i LINK PN IO) controls the slaves (sensors/actuators) connected via AS-i cable. Supported AS?i devicesAS?i master The AS-i block library for SIMATIC PCS 7 supports the following AS-i masters:
1) Only AS?Interface block library for SIMATIC PCS 7 V8 with Advanced Process Library (APL) AS?i slaves Digital AS?i slaves with standard addressing and extended addressing (A/B slaves) are generally suited for deployment on the CM AS?i Master ST, CP 343?2 or CP 343?2P. The CP 343?2 and CP 343?2P AS-i masters transfer I/O data from AS?i slaves with a B address via data records but not via the cyclic process image (partition). To prevent delays in the communication process of the driver blocks for B slaves, we recommend avoiding the use of AS?i slaves with B addresses for SIMATIC PCS 7 configurations with CP 343?2 or CP 343?2P. Digital as well as analog AS?i slaves with standard addressing and extended addressing (A/B slaves) can be operated on the DP/AS?i LINK Advanced or on the IE/AS?i LINK PN IO. DiagnosticsDiagnostics are carried out using faceplates in the SIMATIC PCS 7 Maintenance Station. Faults in the AS?i devices are additionally signaled in plain text. |
| Каталог 2018 | Каталог 2017 | Каталог 2016 | Каталог 2015 | Каталог 2014 | Каталог 2013 | Каталог 2012 | Сертификат | Контакты | Карта сайта | Поиск |


