Recommended line-side componentsSuitable line-side power components are assigned depending on the power rating of the Active Line Modules. The tables below list recommended components. Additional information about the the recommended line-side components can be found in Catalogs IC 10 and LV 10. Assignment of line-side power components to Active Line Modules in chassis formatRated power | Input current | Assignment to Active Interface Module | Assignment to Active Line Module | Bypass connector |
|---|
kW (HP) | A | 6SL3300?... | 6SL3330?... | | 132 (200) | 210 | 7TE32?6AA0 | 7TE32?1AA3 | included in Active Interface Module | 160 (225) | 260 | 7TE32?6AA0 | 7TE32?6AA3 | included in Active Interface Module | 235 (350) | 380 | 7TE33?8AA0 | 7TE33?8AA3 | included in Active Interface Module | 300 (450) | 490 | 7TE35?0AA0 | 7TE35?0AA3 | included in Active Interface Module |
Rated power | Input current | Assignment to Active Interface Module | Switch disconnector without handle and shaft | Switch disconnector with handle and shaft | Cable protection fuse | Cable protection fuse incl. semiconductor protection |
|---|
kW (HP) | A | 6SL3300?... | Article No. | Article No. | Rated current | Article No. | Rated current | Article No. | 132 (200) | 210 | 7TE32?6AA0 | 3KL5530?1AB01 | 3KL5530?1GB01 | 250 A | 3NA3144 | 315 A | 3NE1230?2 | 160 (225) | 260 | 7TE32?6AA0 | 3KL5730?1AB01 | 3KL5730?1GB01 | 315 A | 3NA3252 | 350 A | 3NE1331?2 | 235 (350) | 380 | 7TE33?8AA0 | 3KL5730?1AB01 | 3KL5730?1GB01 | 500 A | 3NA3365 *) | 500 A | 3NE1334?2 | 300 (450) | 490 | 7TE35?0AA0 | 3KL6130?1AB02 | 3KL6130?1GB02 | 630 A | 3NA3372 | 630 A | 3NE1436?2 |
*) Fuse suitable ony for 3KL6130...
|