Standards IEC 60947-4-1, EN 60947-4-1 The contactors are finger-safe according to IEC 60529 (exception: S3 series resistor). The auxiliary conductor and coil terminals are all spring-type terminals. Ambient temperature The permissible ambient temperature for operation of the contactors (across the full coil operating range) is -40 to +70 °C. Power range 3RT contactors are available in all sizes from S00 to S12 up to 250 kW or 500 A (AC-3 at 400 V). Operating range of contactor operating mechanism Sizes S00 to S3 The solenoid coils of the 3RT2 contactors have an extended coil operating range from max. 0.7 to 1.2 x Us and are fitted as standard with surge suppressors. The opening delay is consequently 2 to 5 ms longer than for standard contactors. Sizes S6 to S12 The operating mechanism for the 3RT10 contactors features solid-state control of the contactor coil. Overvoltage damping of the operating mechanism coil is already integrated in the electronics. The operating mechanisms are powered via a supply voltage with an operating range of 0.7 to 1.2 x Us, optionally also controlled depending on the chosen mode of operation. Alternatively, control is via the separate 24 to 110 V DC control signal input. Three rated voltage ranges are available as direct voltage (DC):
|