IM 153-2 High Feature Outdoor | |
Bus connection | |
- Connection for PROFIBUS DP
| 9-pin Sub-D plug, contact assignment as described in IEC 61158/EN 50170, Vol. 2 |
Connectable lower-level components | |
Number of couplers | |
| max. 5 |
| 1 |
Number of PA devices on PROFIBUS PA | max. 64 |
Module-specific data | |
Degree of protection | IP20 |
Transmission rate of the higher level DP master system | 9.6; 19.2; 45.45; 93.75; 187.5; 500 Kbps; 1.5; 3; 6; 12 Mbps |
Communication protocol | PROFIBUS DP |
Frame length | |
| Max. 244 bytes |
| Max. 244 bytes |
| Max. 244 bytes |
- Parameter assignment frame
| Max. 244 bytes |
Voltages, currents, potentials | |
Supply voltage | 24 V DC (20.4 … 28.8 V) |
Reverse polarity protection | Yes |
Voltage failure bridging | 20 ms |
Galvanic isolation | |
- to the higher-level DP master system
| Yes |
- to the DP/PA coupler or Y coupler
| No |
Power consumption of modules (24 V DC) | |
| Max. 200 mA (at 20.4 V) |
| Max. 400 mA (at 20.4 V) |
Power loss of the module | |
| Max. 2.6 W (at 28.8 V) |
| Max. 3.6 W (at 28.8 V) |
Infeed, mechanical design | 4-pin screw terminal, short-circuiting link between PE and M24; the short-circuiting link must be removed for floating operation (independent of this, the DP interface is always floating) |
Status, interrupts, diagnostics | |
Diagnostic displays | |
| Red LED "SF" |
- Bus error on higher level DP master system
| Red LED "BF 1" |
- Bus error on underlying bus system
| Red LED "BF 2" |
- Module is active in redundancy mode
| Yellow LED "ACT" |
- 24 V DC power supply monitoring
| Green "ON" LED |
Climatic conditions | |
Permissible operating temperature | |
| -25 … +60 °C |
| -25 … +40 °C |
Dimensions and weight | |
Dimensions (W ? H ? D) in mm | 40 ? 125 ? 130 |
Weight | approx. 360 g |