Supply voltage | |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes; against destruction |
Short-circuit protection | Yes; Fuse in lower part is exchangeable, the fuse on the IM-LP is not |
Load voltage 2L+ | |
| 24 V |
| Yes; against destruction |
Input current | |
from supply voltage 1L+, max. | 400 mA; Dependent on terminal module, typ. maximum value for FO connection method, full load on RWB and 20.4 V input voltage |
Power loss | |
Power loss, typ. | 6 W; Dependent on terminal module, typ. maximum value for CU connection method, full load on RWB, for FO the value is approx. 0.7 W higher |
Memory | |
Micro Memory Card | No; Internal memory medium |
Address area | |
Addressing volume | |
| 256 byte |
| 256 byte |
Interfaces | |
PROFINET IO | |
| Yes |
| 100 Mbit/s |
| ARP, PING, SNMP |
Interrupts/diagnostics/status information | |
Alarms | |
| Yes; Parameterizable |
| Yes; Parameterizable |
Diagnostics indication LED | |
| Yes; Additional LEDs (MAINT, P1/2 LINK, P1/2 RX/TX) available |
| Yes |
| Yes |
| Yes |
Parameter | |
Swapping interrupt | 1 |
Startup if setpoint not equal to actual configuration | 1 |
Hot swapping of modules | 1 |
Potential separation | |
between backplane bus and electronics | No |
between supply voltage and electronics | Yes |
Isolation | |
Isolation tested with | 707 V DC (type test) |
Degree and class of protection | |
Degree of protection acc. to EN 60529 | |
| Yes |
| Yes |
| Yes |
Ambient conditions | |
Ambient temperature during operation | |
| -25 °C |
| 55 °C |
Ambient temperature during storage/transportation | |
| -40 °C |
| 70 °C |
Dimensions | |
Width | 135 mm |
Height | 130 mm |
Depth | 59.3 mm |
Weights | |
Weight, approx. | 490 g |