Mode of operation and design | |
Measuring principle | Electromagnetic with pulsed constant field |
Empty pipe | Detection of empty pipe (special cable required in remote mounted installation) |
Excitation frequency | Depend on sensor size |
Electrode input impedance | > 1 x 1014 ? |
Input | |
Digital input | 11 … 30 V DC, Ri = 4.4 k? |
| 50 ms |
| I11 V DC = 2.5 mA, I30 V DC = 7 mA |
Output | |
Current output | |
| 4 … 20 mA (active/passive) |
| < 560 ? |
| 0.1 … 30 s, adjustable |
Digital output | |
| 0 … 10 kHz, 50 % duty cycle (uni-/bidirectional) |
| 0.1 … 30 s, adjustable |
| 3 … 30 V DC, max. 110 mA (30 mA Ex version), 200 ? ? Ri ? 10 k? (powered from connected equipment) |
| 0.1 … 30 s, adjustable |
Relay output | |
| Changeover relay, same as current output |
| 42 V AC/2 A, 24 V DC/1 A |
Low flow cut off | 0 … 9.9 % of maximum flow |
Galvanic isolation | All inputs and outputs are galvanic isolated. |
Max. measuring error | |
MAG 6000 I/MAG 6000 I Ex (incl. sensor) | ± 0.2 % ± 1 mm/s |
Rated operation conditions | |
Ambient temperature | |
| |
| -20 … +60 °C (-4 … +140 °F) |
| -20 … +60 °C (14 … 140 °F) |
| -40 … +70 °C (-40 … +158 °F) |
Mechanical load | 18 … 1000 Hz random in x, y, z, directions for 2 hours according to EN 60068-2-36 |
Transmitter: 1.14 g RMS |
Degree of protection | IP67/NEMA 4X to IEC 529 and DIN 40050 (1 mH2O 30 min.) |
EMC performance | IEC/EN 61326-1 (all environments) IEC/EN 61326-2-5 NAMUR NE 21 |
Display and keypad | |
Totalizer | Two eight-digit counters for forward, net or reverse flow |
Display | Background illumination with alphanumeric text, 3 x 20 characters to indicate flow rate, totalized values, settings and faults; Reverse flow indicated by negative sign |
Keypad | Capacitive touch keypad with LED light for feedback indication |
Time constant | Time constant as current output time constant |
Design | |
Enclosure material | Die cast aluminum, with corrosion resistant Basic Polyester powder coating (min. 60 µm) |
| Wall mounting bracket enclosed for remote version |
Dimensions | See dimensional drawings |
Weight | See dimensional drawings |
Power supply | - Standard transmitter: 18 … 90 V DC; 115 … 230 V AC; 50 … 60 Hz
|
- Ex transmitter: 18 … 30 V DC
|
- Ex transmitter: 115 … 230 V AC; 50 … 60 Hz
|
- Ex transmitter NAMUR: 18 … 30 V DC; 115 … 230 V AC; 50 … 60 Hz
|
Power consumption | |
- 24 V DC: 9.6 W, IN = 0.4 A, IST = 1 A (3 ms)
|
Certificates and approvals | |
General purpose | |
Hazardous areas | - ATEX, IECEx, FM, CSA, EAC Ex, NEPSI
- Zone 1 Ex d e [ia] ia IIC T6 Gb
- ATEX, IECEx, CSA
- Zone 21 Ex tD A21 IP67 T85 °C
- FM
- XP IS Class I Div. 1 Groups A, B, C, D
- DIP Class II+III Div. 1 Groups E, F, G
|
Others | - CMC/CPA (China)
- C-TICK (Australia and New Zealand EMC)
- EAC (Russia, Belarus, Kazakhstan)
- KCC (South Korea)
|
Cable entries | |
MAG 6000 I | 2 x M25 (for supply/output) and 2 x M16 (for sensor connection) or 2 x ?" NPT (for supply/output) and 2 x M16 (for sensor connection) |
MAG 6000 I Ex ATEX 2G D | 2 x M20 (for supply/output) and 2 x M16 (for sensor connection) |
Communication | |
Standard versions | HART, Modbus RTU/RS 485, FOUNDATION Fieldbus H1, DeviceNet, PROFIBUS PA, PROFIBUS DP add-on modules |
Ex versions | HART, PROFIBUS PA (not for Ex version) |