N 141/02 - Интерфейсный блок GE 141, шлюз KNX-DALI, 1линия DALI на 64 устройства, монтаж на DIN-рейку
N 141/02
Интерфейсный блок GE 141, шлюз KNX-DALI, 1линия DALI на 64 устройства, монтаж на DIN-рейку
For communication via KNX EIB with electronic ballasts with a DALI interface
DALI output acc. to IEC 60929, for communication with up to 64 DALI ballasts
Integrated power supply with input voltage AC/DC 110...240 V, 50...400 Hz, for powering the gateway electronics and DALI output
Maximum DALI output voltage of 16 V, short circuit resistant
Green LED for displaying the operating voltage
Pushbutton for switching between bus and direct operating mode
Yellow LED for displaying direct mode
One pair of push buttons for switching On/Off of all connected DALI ballasts
One red LED in the switching button for displaying the switching state of all DALI ballasts (permanent LED light) and displaying a DALI fault condition by blinking
Control (switching, dimming, and setting dimming value) as well as feedback of status and lamp failure of up to 64 DALI ballasts
Operation of each DALI ballast either as individual device or as member of one of up to 16 DALI groups
Configurable assignment of the DALI ballasts to up to 16 DALI groups, which can only be switched and dimmed in groups including reporting status and lamp failures in groups
Control (switching, dimming, setting dimming value) of self-contained emergency luminaires as individual luminaires or as member of a DALI group
Distinction between self-contained emergency luminaires with one or two DALI devices
Starting the self-conducted testing of each individual inverter and reporting the test result via bus
Distinction between function test, short duration test, and long duration test
Optional configuration of any DALI ballast to dim to a preset dimming value in case of emergency mode
Locking of switching and dimming commands as well as configuration while emergency mode is activated
Activation of emergency mode based on a configurable number of failed DALI ballasts
Transformation of dimming commands into a temporary set point adjustment for ballasts with integrated constant light level control and directly connected light level sensor
One or two level timer
Integrated scene control for up to 16 scenes
Integrated one time or cyclical control of repeatable sequences or color effects
Possible assignment of a CIN to a DALI ballast and with commissioning of DALI ballasts and test of channel, scene, and effect functionality within ETS
Integrated bus coupling unit
Only half a standard bus load
Bus connection via bus terminal or contact system to data rail