Product type designation | | |
Input current | | |
from backplane bus 5 V DC, typ. | 50 mA | 50 mA |
Output voltage | | |
Power supply to the transmitters | | |
| 4 mA; per channel | 4 mA; per channel |
Power losses | | |
Power loss, typ. | 1 W | 1 W |
Digital inputs | | |
Number of digital inputs | 4; Current-sourcing | 4; Current-sourcing |
| 1 | 1 |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes | |
Input characteristic curve in accordance with IEC 61131, type 2 | | Yes |
Number of simultaneously controllable inputs | | |
all mounting positions | | |
| 4 | 4 |
Input voltage | | |
| DC | DC |
| 5 V | 24 V |
| 0 to 1 V | 0 to 5 V |
| 2 to 6 V | |
Input current | | |
| 3 mA | 2 mA |
| 6 mA | 5.8 mA |
| | 14 mA |
Input delay (for rated value of input voltage) | | |
for standard inputs | | |
| Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four |
| 2 µs | 2.5 µs |
for interrupt inputs | | |
| Yes | Yes |
for counter/technological functions | | |
| Yes | Yes |
Cable length | | |
| 50 m; shielded, twisted pair | 50 m; Standard input: 500 m, high-speed counters: 50 m |
Digital outputs | | |
Number of digital outputs | 0 | 0 |
short-circuit protection | No | No |
Interrupts/diagnostics/status information | | |
Alarms | | |
| Yes | Yes |
Diagnostic messages | | |
| Yes | Yes |
Diagnostics indication LED | | |
| Yes | Yes |
Degree and class of protection | | |
Degree of protection to EN 60529 | | |
| Yes | Yes |
Standards, approvals, certificates | | |
Marine approval | | |
| Yes | Yes |
Ambient conditions | | |
Free fall | | |
| 0.3 m; five times, in dispatch package | 0.3 m; five times, in dispatch package |
Ambient temperature in operation | | |
| 0 °C to 55 °C horizontal installation, 0 °C to 45 °C vertical installation | -20 °C to +60 °C horizontal mounting, -20 °C to 50 °C vertical mounting, 95% humidity, non-condensing |
| 0 °C | -20 °C |
| 55 °C | 60 °C |
Storage/transport temperature | | |
| -40 °C | -40 °C |
| 70 °C | 70 °C |
Air pressure acc. to IEC 60068-2-13 | | |
| 660 hPa | 660 hPa |
| 1 080 hPa | 1 080 hPa |
Relative humidity | | |
| 95 % | 95 % |
Mechanics/material | | |
Type of housing (front) | | |
| Yes | Yes |
Dimensions | | |
Width | 38 mm | 38 mm |
Height | 62 mm | 62 mm |
Depth | 21 mm | 21 mm |
Weights | | |
Weight, approx. | 40 g | 40 g |