SITRANS I200 output isolator with HART |
Input | |
Input signal | 0/4 ... 20 mA with HART |
Functional range | 0 ... 24 mA |
Max. input current | 50 mA |
Input resistance (changeable switch LI) | 225 ?/550 ? |
Communication signal | Bidirectional HART transmission, 0.5 kHz ... 30 kHz |
Ex i output | |
Output signal | 0/4 ... 20 mA with HART |
Connectable load resistance | 0 ... 800 ? |
Min. load resistance for short-circuit monitoring | 150 ? |
Residual ripple | ? 50 mV |
No-load voltage | ? 25.6 V |
Response time (10% ... 90%) | ? 100 ?s |
Transmission characteristics Input/output | 1:1 (0 ... 20 mA --> 0 ... 20 mA, 4 ... 20 mA --> 4 ... 20 mA) |
Measuring accuracy Accuracy, typical data expressed as % of calibrated span at UN, 23 °C | |
Linearity error | ? 0.1% |
Offset error | ? 0.1% |
Temperature influence | ? 0.1%/10 K |
Power supply effect within voltage range | ? 0.01% |
Load resistance effect | ? 0.02% |
Rated conditions | |
Degree of protection of enclosure | IP30 |
Degree of protection of terminals | IP20 |
Ambient conditions | |
| -20 °C ... +70 °C (-4 ... +158 °F) (see "Operating instructions") |
| -40 °C ... +80 °C (-40 ... +176 °F) |
- Relative humidity (no condensation)
| ? 95% |
Electromagnetic compatibility | Tested under the following standards and regulations: EN 61326-1 Use in the industrial environment |
Design | |
Screw terminals | |
| |
| 0.2 ... 2.5 mm2 (0.00031 ... 0.0039 in2) |
| 0.2 ... 2.5 mm2 (0.00031 ... 0.0039 in2) |
- Flexible with end ferrules (without/with plastic ferrule)
| 0.25 ... 2.5 mm2 (0.00039 ... 0.0039 in2) |
| |
| 0.2 ... 1 mm2 (0.00031 ... 0.00155 in2) |
| 0.2 ... 1.5 mm2 (0.00031 ... 0.0023 in2) |
- Flexible with end ferrules
| 0.25 ... 1 mm2 (0.00039 ... 0.00155 in2) |
Weight | Approx. 160 g (0.35 lb) |
Type of installation | On DIN rail according to EN 50022 (NS35/15; NS35/7.5) |
Mounting position | Vertical or horizontal |
Enclosure material | PA 6.6 |
Fire protecting class (UL-94) | V0 |
Auxiliary power | |
Rated voltage UN | 24 V DC |
Voltage range | 18 ... 31.2 V |
Residual ripple within voltage range | ? 3.6 VSS |
Rated current (UN, 20 mA) | 80 mA |
Power consumption (UN, 20 mA) | 1.3 W |
Power loss (at UN, RL = 500 ?) | 1.1 W |
Operation indicator | Green "PWR" LED |
Reverse polarity protection | Yes |
Undervoltage monitoring | Yes (no faulty module/output states) |
Electrical isolation | |
- Test voltage according to EN 60079-11
| |
| 1.5 kV AC |
- Ex i output to auxiliary power
| 1.5 kV AC |
- Error contact to Ex i output
| 1.5 kV AC |
- Test voltage according to EN 50178
| |
| 350 V AC |
- Error contact to auxiliary power and input
| 350 V AC |
Error detection Ex i output | |
| > 10 k? |
| < 15 ? |
| > 100 k? |
- Open-circuit detection only for input current
| ? 3.6 mA |
| Activated/deactivated |
| LED red "LF" |
- Error messaging and power supply failure
| - Contact (30 V/100 mA), closed to ground in case of error
- pac-Bus, floating contact (30 V/100 mA)
|
Certificates and approvals | |
Explosion protection ATEX | |
- EC type-examination certificate
| DMT 03 ATEX E 012 X |
| II 3 (1) G Ex nA nC [ia] IIC T4 II (1) D [Ex iaD] |
Installation | In Zone 2, Div. 2 and in the safe area |
Other approvals | USA (FM) Canada (CSA) Shipping (DNV) |
Safety specifications (CENELEC) | |
| 25.6 V |
| 96 mA |
| 605 mW |
- Max. connectable capacitance Co for IIC/IIB
| 103 nF/800 nF |
- Max. connectable inductance Lo for IIC/IIB
| 1.9 mH/11 mH |
- Internal capacitance Ci and inductance Li
| Negligible |
| 253 V |
- Additional information and value combinations
| See Certifications |