Rated power 1) | | | | | | | |
- Based on the base-load current IL
| | | | | | | |
| kW | 160 | 200 | 250 | 315 | 355 | 400 |
| hp | 200 | 250 | 300 | 400 | 450 | 500 |
- Based on the base-load current IH
| | | | | | | |
| kW | 132 | 160 | 200 | 250 | 250 | 315 |
| hp | 150 | 200 | 200 | 300 | 300 | 350 |
Output current at 50 Hz 3 AC | | | | | | | |
- Rated current Irated (400 V ±10 %)
| A | 300 | 370 | 460 | 585 | 655 | 735 |
- Rated current Irated (480 V ±10 %)
| A | 245 | 308 | 369 | 487 | 526 | 602 |
- Base-load current IL (400 V ±10 %) 2)
| A | 290 | 360 | 450 | 570 | 640 | 720 |
- Base-load current IL (480 V ±10 %) 2)
| A | 240 | 302 | 361 | 477 | 515 | 590 |
- Base-load current IH (400 V ±10 %) 3)
| A | 240 | 296 | 368 | 468 | 491 | 551 |
- Base-load current IH (480 V ±10 %) 3)
| A | 196 | 247 | 295 | 390 | 394 | 452 |
| A | 392 | 486 | 608 | 770 | 864 | 972 |
Rated pulse frequency | kHz | 2 | 2 | 2 | 2 | 2 | 2 |
Input current 4) | | | | | | | |
- Rated current Irated (400 V ±10 %)
| A | 317 | 375 | 469 | 597 | 668 | 750 |
- Rated current Irated (480 V ±10 %)
| A | 262 | 314 | 376 | 497 | 536 | 614 |
- Base-load current IL (400 V ±10 %) 2)
| A | 307 | 365 | 459 | 585 | 654 | 735 |
- Base-load current IL (480 V ±10 %) 2)
| A | 257 | 308 | 368 | 486 | 525 | 602 |
- Base-load current IH (400 V ±10 %) 3)
| A | 254 | 300 | 375 | 477 | 501 | 562 |
- Base-load current IH (480 V ±10 %) 3)
| A | 210 | 251 | 301 | 397 | 402 | 461 |
| A | 415 | 493 | 620 | 785 | 881 | 992 |
Short-circuit current rating per IEC, in conjunction with the specified fuses | kA | 100 | 100 | 100 | 100 | 100 | 100 |
Rated short-circuit current SCCR (Short Circuit Current Rating) in accordance with UL508C (up to 600 V), in conjunction with the specified fuses | kA | 100 | 100 | 100 | 100 | 100 | 100 |
Minimum short-circuit current 5) | | | | | | | |
| A | 4400 | 5200 | 6300 | 9000 | 10000 | 12000 |
| A | 9500 | 14000 | 20000 | 20000 | 30000 | 30000 |
Efficiency ? At rated current Irated (400 V/40 °C) | | 0.98 | 0.98 | 0.981 | 0.981 | 0.98 | 0.981 |
Power loss At rated current Irated (400 V/40 °C) | kW (hp) | 3.642 | 4.414 | 5.125 | 6.791 | 7.687 | 8.385 |
Coolant requirements | m3/s (ft3/s) | 0.21 | 0.21 | 0.21 | 0.36 | 0.36 | 0.36 |
Coolant | | of air | of air | of air | of air | of air | of air |
Sound pressure level LpA (1 m) | dB | 74 | 74 | 74 | 74 | 74 | 74 |
Power requirement 24 V DC supply | A | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
Line supply connection U1/L1, V1/L2, W1/L3 | | M12 screw | M12 screw | M12 screw | M12 screw | M12 screw | M12 screw |
- Conductor cross section, max. (IEC)
| mm2 | 2 ? 240 | 2 ? 240 | 2 ? 240 | 4 ? 240 | 4 ? 240 | 4 ? 240 |
Motor connection U2, V2, W2 | | M12 screw | M12 screw | M12 screw | M12 screw | M12 screw | M12 screw |
- Conductor cross section, max. (IEC)
| mm2 | 2 ? 240 | 2 ? 240 | 2 ? 240 | 4 ? 240 | 4 ? 240 | 4 ? 240 |
DC link connection DCP, DCN | | M12 screw | M12 screw | M12 screw | M12 screw | M12 screw | M12 screw |
- Conductor cross section, max. (IEC)
| mm2 | 2 ? 240 | 2 ? 240 | 2 ? 240 | 4 ? 240 | 4 ? 240 | 4 ? 240 |
PE/GND connection | | M12 screw | M12 screw | M12 screw | M12 screw | M12 screw | M12 screw |
- Conductor cross section, max. (IEC)
| mm2 | 3 ? 240 | 3 ? 240 | 3 ? 240 | 6 ? 240 | 6 ? 240 | 6 ? 240 |
Cable length, max. between Power Module and motor | | | | | | | |
- When compliant with categories C2 and C3 according to EN 61800-3
shielded
| m (ft) | 100 | 100 | 100 | 100 | 100 | 100 |
- When non-compliant with the limit values for RI suppression and without output reactor or dv/dt filter
unshielded
| m (ft) | 200 | 200 | 200 | 200 | 200 | 200 |
- When non-compliant with the limit values for RI suppression with output reactor or dv/dt filter
shielded/unshielded
| m (ft) | 300/450 | 300/450 | 300/450 | 300/450 | 300/450 | 300/450 |
Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 |
Dimensions | | | | | | | |
| mm (in) | 452 | 452 | 452 | 548 | 548 | 548 |
| mm (in) | 1447 | 1447 | 1447 | 1696 | 1696 | 1696 |
| mm (in) | 327.5 | 327.5 | 327.5 | 393 | 393 | 393 |
Frame size | | GX | GX | GX | HX | HX | HX |
Weight, approx. | kg (lb) | 101 | 102 | 107 | 155 | 155 | 157 |
Minimum size of control cabinet for installation of a Power Module | | | | | | | |
| mm (in) | No specifications | No specifications | No specifications | 800 | 800 | 800 |
| mm (in) | No specifications | No specifications | No specifications | 2000 | 2000 | 2000 |
| mm (in) | No specifications | No specifications | No specifications | 600 | 600 | 600 |