System operating voltage | 380 ... 480 V ±10 % 3 AC |
Grid requirement Short-circuit power RSC | >25 >100 line reactor recommended |
Input frequency | 47 ... 63 Hz |
Output frequency | |
| 0 ... 550 Hz |
| 0 ... 240 Hz |
Pulse frequency | 75 kW (HO): 4 kHz as of 90 kW (HO): 2 kHz Higher pulse frequencies up to 16 kHz, see derating data |
Power factor ? | 0.7 ... 0.85 |
Offset factor cos ? | 0.95 |
Inverter efficiency | 95 ... 98 % |
Output voltage, max. As % of input voltage | 95% |
Overload capability | |
Note: When the overload capability is used, the base-load current IL is not reduced. | 90 kW (LO): 1.5 ? base-load current IL (i. e. 150 % overload) for 3 s plus 1.1 ? base-load current IL (i. e. 110 % overload) for 57 s within a cycle time of 300 s 110 kW and higher (LO): 1.5 ? base-load current IL (i. e. 150 % overload) for 1 s plus 1.1 ? base-load current IL (i. e. 110 % overload) for 59 s within a cycle time of 300 s |
Note: When the overload capability is used, the base-load current IH is not reduced. | 75 kW (HO): 2 ? base-load current IH (i. e. 20 % overload) for 3 s plus 1.5 ? base-load current IH (i. e. 150 % overload) for 57 s within a cycle time of 300 s 90 kW and higher (HO): 1.6 ? base-load current IH (i. e. 160 % overload) for 3 s plus 1.36 ? base-load current IH (i. e. 136 % overload) for 57 s within a cycle time of 300 s |
Electromagnetic compatibility | - Devices without line filter
- Devices with line filter class A for compliance with conducted and radiated interference requirements of Category C2
|
Possible braking methods | - DC braking
- Dynamic braking with integrated braking module
|
Degree of protection | IP20 |
Operating temperature | |
| 0 ... 40 °C (32 ... 104 °F) without derating >40 ... 60 °C (>104 ... 140 °F) see derating characteristics |
| 0 ... 50 °C (32 ... 122 °F) without derating >50 ... 60 °C (>122 ... 140 °F) see derating characteristics |
Storage temperature | -40 ... +70 °C (-40 ... +158 °F) |
Relative humidity | <95 % RH, condensation not permissible |
Cooling | Internal ventilation, power units with increased air cooling by built-in fans |
Installation altitude | Up to 1000 m (3281 ft) above sea level without derating, > 1000 m (3281 ft) see derating characteristics |
Protection functions | - Undervoltage
- Overvoltage
- Overcurrent/overload
- Ground fault
- Short-circuit
- Stall protection
- Motor blocking protection
- Motor overtemperature
- Inverter overtemperature
- Parameter locking
|
Rated short-circuit current SCCR (Short-Circuit Current Rating) 1) | 65 kA |
Compliance with standards | UL, cUL, CE, C-Tick, SEMI F47 |
CE marking | According to Low-Voltage Directive No. 2006/95/EC, EMC Directive 2004/108/EC |