380 ... 480 V 3 AC ±10 % (in operation -15 % < 1 min)
Line frequency
47 … 63 Hz
SCCR (short-circuit current rating)
65 kA in conjunction with the recommended fuses class J or circuit breakers in accordance with UL489 / CSA 22.2 No. 5-02
see recommended line-side components
Line power factor
at rated power
Fundamental Power factor (cos ?1)
> 0.96
Total (?)
0.75 … 0.93
Overvoltage category
to EN 60664?1
Class III
DC link voltage, approx.
1.35 x line voltage1)
Electronics power supply
24 V DC, -15 %/+20 %
Radio interference suppression
Standard
20 kW and 40 kW Basic Line Modules
No radio interference suppression
100 kW Basic Line Module
Category C3 to EN 61800?3 Total cable length up to 350 m (1148 ft) (shielded)
With line filter
Category C2 to EN 61800?3 Total cable length up to 350 m (1148 ft) (shielded)
Type of cooling
Internal air cooling, power units with forced air cooling using a built-in fan
Cold plate cooling
Permissible ambient and coolant temperature (air)
during operation for line-side components, Line Modules and Motor Modules
0 … 40 °C (32 … 104 °F) without derating, > 40 … 55 °C (104 … 131 °F) see derating characteristics
Installation altitude
Up to 1000 m (3281 ft) above sea level without derating, > 1000 ... 4000 m (3281 ... 13124 ft) above sea level, see derating characteristics
Conformity
CE (Low Voltage and EMC Directives)
Approvals, according to
cULus
1) The DC link voltage is unregulated and load-dependent. For further information see chapter System description – Dimensioning.
Line voltage 380 ... 480 V 3 AC
Basic Line Modules in booksize format
Internal air cooling
6SL3130-1TE22-0AA0
6SL3130-1TE24-0AA0
6SL3130-1TE31-0AA0
Cold plate cooling
6SL3136-1TE22-0AA0
6SL3136-1TE24-0AA0
6SL3136-1TE31-0AA0
Power
Rated power Prated
At 380 V 3 AC
kW
20
40
100
At 460 V 3 AC 2)
(HP)
(25)
(50)
(125)
For S6 duty (40 %) PS6
kW
26
52
130
Pmax
kW
60
120
175
Braking power
with external braking resistor
PBmax. (= 2 ? Prated)
kW
40
80
–
Continuous braking power Pd (= 0.25 ? Pn)
kW
5
10
–
DC link current
At 600 V DC
A
34
67
167
For S6 duty (40 %)
A
43
87
217
Maximum
A
100
200
292
Input current
Rated current at 380 V 3 AC
A
35
69
172
Maximum
A
113
208
301
Activation threshold
Braking chopper
V
774
774
–
Resistance value
of the external braking resistor
?
? 14.8
? 7.4
–
Cable length, max.
to braking resistor
m (ft)
15 (50)
15 (50)
–
Connection for braking resistor (X2)
Screw-type terminals
Screw-type terminals
–
Conductor cross-section, max.
mm2
0.5 … 4
0.5 … 10
Power requirement, max
24 V DC electronics power supply
A
1
1.4
2
Current carrying capacity
24 V DC busbars
A
20
20
20
DC link busbars
A
100
200
200
DC link capacitance
Basic Line Module
?F
940
1880
4100
Drive line-up, max.
?F
20000
20000
50000
Internal air cooling
Power loss 1)
kW
0.144
0.284
0.628
Cooling air requirement
m3/s (ft3/s)
0.016 (0.565)
0.031 (1.095)
0.05 (1.77)
Sound pressure level LpA (1 m)
dB
< 60
< 65
< 65
Cold plate cooling
Power loss, int./ext. 1)
kW
0.047/0.095
0.071/0.205
0.168/0.45
Thermal resistance Rth
K/W
0.075
0.05
0.045
Line connection
U1, V1, W1
Screw-type terminals
Screw-type terminals
M8 screw stud
Conductor cross-section, max.
mm2
0.5 … 16
10 … 50
1 ? 35 … 120 or 2 ? 50
Shield connection
Integrated into the power plug
See Accessories
See Accessories
PE connection
M5 screw
M6 screw
M6 screw
Cable length, max.
(total of all motor power cables and DC link)
Shielded/unshielded
m (ft)
1000/1500 (3281/4921) (above 630/850 m (2067/2789 ft) with Voltage Clamping Module)
1000/1500 (3281/4921) (above 630/850 m (2067/2789 ft) with Voltage Clamping Module)
1000/1500 (3281/4921) (above 630/850 m (2067/2789 ft) with Voltage Clamping Module)
Degree of protection
IP20
IP20
IP20
Dimensions
Width
mm (in)
100 (3.94)
150 (5.91)
200 (7.87)
Height
mm (in)
380 (15.0)
380 (15.0)
380 (15.0)
Depth
With internal air cooling
mm (in)
270 (10.6)
270 (10.6)
270 (10.6)
With cold plate cooling
mm (in)
226 (8.90)
226 (8.90)
226 (8.90)
Weight, approx.
With internal air cooling
kg (lb)
6.8 (15)
11.3 (25)
15.8 (35)
With cold plate cooling
kg (lb)
6.4 (14)
10.9 (24)
16.4 (36)
1) Power loss of Basic Line Module at rated output including losses of 24 V DC electronics power supply.
2) Nominal HP ratings are provided for ease of assigning components only. The Line Module outputs are dependent on the Motor Module loading and are to be dimensioned accordingly.