| | SIPLUS master interface module for IM 151 CPU |
Article No. | 6AG1 138-4HA00-7AB0 |
BasedOn Article No. | 6ES7 138-4HA00-0AB0 |
Ambient temperature range | -25 °C … +70 °C |
Conformal coating | Coating of the printed circuit boards and the electronic components |
Technical data | The technical data of the standard product applies except for the ambient conditions. |
Ambient conditions |
Relative humidity | 100%, condensation/frost permitted. No commissioning in bedewed state. |
Biologically active substances, compliance with EN 60721-3-3 | Class 3B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation! |
Chemically active substances, compliance with EN 60721-3-3 | Class 3C4 incl. salt spray in accordance with EN60068-2-52 (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation! |
Mechanically active substances, compliance with EN 60721-3-3 | Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation! |
Air pressure (depending on the highest positive temperature range specified) | 1 080 ... 795 hPa (-1 000 … +2 000 m) See ambient temperature range 795 ... 658 hPa (+2 000 ... +3 500 m) derating 10 K 658 … 540 hPa (+3 500 … +5 000 m) derating 20 K |