Classification | Class I Division 2 |
Enclosure dimensions (in mm) | 444 x 438 x 275 |
Enclosure volume (I) | Approx. 50 l |
Enclosure pressure (normal) | 1 hPa |
FM certificate | Certificate of compliance 1X8A4.AE / 0B3A3.AE |
Reaction upon failure of pressure | Opening of switching contact, and alarm via signal indicator (red display) |
System type | MiniPurge complete system |
Operating mode | Continuous purging |
Type of enclosure | Reinforced polycarbonate |
Enclosure surface | RAL 7035 gray with transparent cover |
Pressure supply | Dry, oil-free air or inert gas with regulated pressure of approx. 2000 hPa (30 psi) at inlet of MiniPurge |
Supply connections | Pressure via ? BSPP connection, pressure hose at least ?" or 12 mm |
Display (signal indicator) | Pneumatically driven color signal: green/red |
Switching contact | Via SPCO switch approved for Class 1 Division 2 |
Settings | Lower response limit 0.5 hPa set relative to purging gas flow of 1 … 2 l/min |
Prepurging time | Is defined by operator, and controlled manually |
Enclosure pressure limitation | By means of stainless steel with integrated flame arrestor; opens at 10 hPa ± 10% |