Product designation | | - | Power module LA724I | Power module LA724I HP | - | Line voltage compensation NE724 | Fan module LM724 | SM724I current measuring module |
General technical data: | | | | | | | | |
Equipment marking / acc. to DIN EN 81346-2 | | K | Q | K | T | G | T |
Degree of pollution | | 2 |
Certificates/ approvals: | | | | | | | | |
Certificate of suitability | | CE, KCC |
Supply voltage: | | | | | | | | |
Type of voltage / of the supply voltage | | AC | NO_DATA | AC | NO_DATA |
Supply voltage / with AC / Rated value | V | 230 | 400 | NO_DATA | 230 | NO_DATA |
| % | 18 | NO_DATA | 18 | NO_DATA |
| % | 15 | NO_DATA | 15 | NO_DATA |
Type of electrical connection / for supply voltage | | Terminal, 2-pole | Bus bar or ring cable lug | 4 connecting cables with ring cable lug | Connector, 2-pole | Terminal, 16-pole |
Communication: | | | | | | | | |
Design of the interface | | PROFIBUS DP | system interface | NO_DATA |
Mechanical data: | | | | | | | | |
mounting position | | vertical | horizontal | vertical |
Mounting type | | Screws in fixing lugs at top and bottom | NO_DATA | Mounting clips | Screws in fixing lugs at top and bottom |
Type of ventilation | | Self ventilation or forced ventilation | Self-ventilation | Self ventilation or forced ventilation |
Shock resistance | | | | | | | | |
| | 15g / 11 ms / 3 shocks / axis |
| | 25 g / 6 ms / 1000 shocks / axis |
Vibration resistance | | | | | | | | |
| | 10 ... 58 Hz / 0.15 mm, 58 ... 150 Hz / 1g |
| | 5 ... 9 Hz / 3.5 mm, 9 ... 500 Hz / 1g |
Protection class IP | | IP20 |
Width | mm | 50 | 86 | 100 | 150 |
Height | mm | 480 | 22 | 50 | 77.5 |
Depth | mm | 210 | 160 | 162 | 115 |
Electromagnetic compatibility: | | | | | | | | |
Conducted interference / due to burst / acc. to IEC 61000-4-4 | | 2 kV voltage supply cables / 2 kV signal cables |
Conducted interference / due to surge / acc. to IEC 61000-4-5 | | On supply lines: 1 kV symmetrical, 2 kV asymmetrical, PROFIBUS cable asymmetrical 1 kV | on power supply and signal cables: 1 kV symmetrical, 2 kV unsymmetrical |
Conducted interference / due to high-frequency radiation / acc. to IEC 61000-4-6 | | 10 V (0.15 ... 80 MHz) |
Electrostatic discharge / acc. to IEC 61000-4-2 | | 4 kV contact discharge / 8 kV air discharge |
Field-bound parasitic coupling / acc. to IEC 61000-4-3 | | 10 V/m (80 ... 1000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m (2.0 ... 2.7 GHz) |
EMC emitted interference | | Limit value class A to EN 55011 group 1 |
Overvoltage category | | III |
Ambient conditions: | | | | | | | | |
Ambient temperature | | | | | | | | |
| °C | 0 ... 55 |
| °C | -40 ... +70 |
| °C | -40 ... +70 |
Air pressure | | | | | | | | |
| hPa | 860 ... 1 080 |
| hPa | 660 ... 1 080 |
Installation altitude / at height above sea level / maximum | m | 2 000 |
Relative humidity / at 25 °C / maximum | % | 95 |