Product
|
SITOP UPS1100 battery module 24 V, 1.2 Ah
|
SITOP UPS1100 battery module 24 V, 3.2 Ah
|
SITOP UPS1100 battery module 24 V, 7 Ah
|
SITOP UPS1100 battery module 24 V, 12 Ah
|
SITOP UPS1100 battery module 24 V, 2.5 Ah high-temperature
|
|
For SITOP UPS1600
|
10 A
|
10 A and 20 A
|
10 A and 20 A
|
20 A and 40 A
|
10 A
|
|
Article No.
|
6EP4131-0GB00-0AY0
|
6EP4133-0GB00-0AY0
|
6EP4134-0GB00-0AY0
|
6EP4135-0GB00-0AY0
|
6EP4132-0GB00-0AY0
|
|
Recommended end of charge voltage (set automatically by SITOP UPS1600):
|
26.4…27.3 V DC (> +20 °C), 27.3…29.0 V DC (< +20 °C)
|
26.4…27.3 V DC (> +20 °C), 27.3…29.0 V DC (< +20 °C)
|
26.4…27.3 V DC (> +20 °C), 27.3…29.0 V DC (< +20 °C)
|
26.4 … 27.3 V DC (> +20 °C), 27.3 … 29.0 V DC (< +20 °C)
|
29 V (-10 °C); 28.6 V (0 °C), 28.3 V (+10 °C); 27.9 V (+20 °C); 27.2 V (+40 °C); 26.8 V (+50 °C) 26.4 V (+60 °C)
|
|
Charging current
|
max. 0.3 A
|
max. 0.8 A
|
max. 1.75 A
|
max. 3 A
|
max. 5 A
|
|
Rated output voltage
|
24 V DC, 22...27.0 V DC (no load)
|
24 V DC, 22...27.0 V DC (no load)
|
24 V DC, 22...27.0 V DC (no load)
|
24 V DC, 22...27.0 V DC (no load)
|
24 V DC, 22...27.0 V DC (no load)
|
|
Rated output current
|
10 A
|
20 A
|
40 A
|
40 A
|
20 A
|
|
Integral battery fuse
|
15 A
|
25 A
|
2 x 25 A
|
2 x 25 A
|
25 A
|
|
Signaling
|
LED green: Battery OK, flashing green: Error or warning, OFF: No communication
|
LED green: Battery OK, flashing green: Error or warning, OFF: No communication
|
LED green: Battery OK, flashing green: Error or warning, OFF: No communication
|
LED green: Battery OK, flashing green: Error or warning, OFF: No communication
|
LED green: Battery OK, flashing green: Error or warning, OFF: No communication
|
|
Degree of protection (EN 60529)
|
IP00
|
IP00
|
IP00
|
IP00
|
IP00
|
|
Ambient temperature
|
0…+40 °C
|
0…+40 °C
|
0…+40 °C
|
0…+40 °C
|
-40 … +60°C
|
|
Transport/storage temperature
|
-20 …+50°C
|
-20 …+50°C
|
-20 …+50°C
|
-20 …+50°C
|
-40 … +60°C
|
|
Service life (when capacity falls to 50 % of original capacity), depending on battery temperature, approx.
|
+20 °C: 4 years, +30 °C: 2 years, +40 °C: 1 year, +50 °C: 0.5 years
|
+20 °C: 4 years, +30 °C: 2 years, +40 °C: 1 year, +50 °C: 0.5 years
|
+20 °C: 4 years, +30 °C: 2 years, +40 °C: 1 year, +50 °C: 0.5 years
|
+20 °C: 4 years, +30 °C: 2 years, +40 °C: 1 year, +50 °C: 0.5 years
|
+20 °C: 10 years, +30 °C: 7 years, +40 °C: 3 years, +50 °C: 1.5 years, +60 °C: 1 year
|
|
Installation
|
DIN rail or wall mounting
|
DIN rail or wall mounting
|
Wall mounting
|
Wall mounting
|
DIN rail or wall mounting
|
|
Dimensions (W x H x D) in mm
|
89 x 130 x 107
|
190 x 169 x 79.5
|
186 x 186 x 110.5
|
253 x 168 x 110.5
|
265 x 115 x 63
|
|
Weight, approx.
|
1.9 kg
|
3.8 kg
|
6.1 kg
|
9.3 kg
|
3.7 kg
|
|
Certifications
|
CE, cURus-recognized, C-Tick; KCC; GL, ABS, ATEX
|
CE, cURus-recognized, C-Tick; KCC; GL, ABS, ATEX
|
CE, cURus-recognized, C-Tick; KCC; GL, ABS, ATEX
|
CE, cURus-recognized, C-Tick; KCC; GL, ABS, ATEX
|
CE, cURus-recognized, C-Tick; KCC; GL, ABS, ATEX
|