![]() ? During IEC 61850 MMS communication with the IEDs (protective equipment), the station controller acts like an IEC 61850 MMS client. The IEDs are IEC 61850 MMS servers. All IEC 61850 tags in the IED can be addressed via the station controller. Time stamp, value, and status of the tags are transferred depending on the configuration. The time stamp always originates from the protective equipment. Configuration is carried out in the CFC Editor with predefined blocks from the supplied SG_LINK communications library. The blocks available for various types of device are preparameterized for a standard scope of tags, but can also be reparameterized without problem for special project requirements. The station gateway communicates with the SIMATIC PCS 7 automation system via its CP 443?1 communication module, and uses the standard communication mechanisms of SIMATIC PCS 7 (BSEND/BRECV). The communication blocks with integrated connection diagnostics can be positioned in the CFC Editor on a CFC chart. A changed connection status, e.g. failure or re-establishment, is signaled in the SIMATIC PCS 7 Operator System by means of an alarm. |