Product name
|
SINAMICS G120 PM250 Power Modules
|
| |
6SL3225-0BE25-5AA1
|
6SL3225-0BE27-5AA1
|
6SL3225-0BE31-1AA1
|
6SL3225-0BE31-5AA0
|
|
System operating voltage
|
380 ... 480 V 3 AC ± 10 %
|
|
Line supply requirements Line short circuit voltage Uk
|
U
k < 1 %
|
|
Input frequency
|
47 ... 63 Hz
|
|
Degree of protection
|
IP20
|
|
Possible braking methods
|
Regenerative feedback in generator mode
|
|
Connectable motors
|
Standard motors
|
|
Output frequency for control type Vector
|
0 ... 200 Hz
|
|
Power factor
|
0.9
|
|
Efficiency ?
|
0.95
|
|
Overload capability
|
2 ? rated output current (i.e. 200 % overload) for 3 s with a cycle time of 300 s
|
|
Electromagnetic compatibility
|
Line filter class A acc. to EN 55011
|
|
Ambient temperature
|
0 ... 50 °C without derating, > 50 ... 60 °C derating to 75 %
|
|
Storage temperature
|
-40 ::: +70 °C
|
|
Relative humidity
|
< 95 % RH, condensation not permissible
|
|
Cooling
|
Internal ventilation, power units with increased air cooling by built-in fans
|
|
Cooling clearance
|
|
|
Top/bottom
|
125 mm
|
|
Front
|
0 mm
|
|
Side
|
50 mm
|
|
Installation altitude
|
Up to 1000 m without derating, > 1000 ... 2000 m derating to 93 %
|
|
Compliance with standards
|
UL, cUL, CE, c-tick
|
|
CE marking
|
According to Low-Voltage Directive 2006/95/EC
|
|
Output current at 50 Hz 400 V 3 AC
|
|
|
|
|
|
|
18 A
|
25 A
|
32 A
|
36 A
|
|
|
13.2 A
|
19 A
|
26 A
|
32 A
|
|
Rated power
Based on IL Based on IH1)
|
7.5 kW
|
11 kW
|
15 kW
|
18.5 kW
|
|
Rated pulse frequency
|
4 kHz
|
4 kHz
|
4 kHz
|
4 kHz
|
|
Power loss at rated current
|
0.24 kW
|
0.3 kW
|
0.4 kW
|
0.44 kW
|
|
Cooling air requirement
|
0.038 m3/s
|
0.038 m3/s
|
0.038 m3/s
|
0.022 m3/s
|
|
Input current
|
13.2 A
|
19 A
|
26 A
|
30 A
|
|
Line supply connection
U1/L1, V1/L2, W1/L3
|
Screw terminals
|
|
|
2.5 ... 10 mm2
|
|
PE connection
|
On housing with M5 screw
|
|
Motor cable length, max.
|
|
|
|
25 m
|
25 m
|
25 m
|
50 m
|
|
|
100 m
|
100 m
|
100 m
|
100 m
|
|
Dimensions
|
|
|
|
|
|
|
189 mm
|
189 mm
|
189 mm
|
275 mm
|
|
|
334 mm
|
334 mm
|
334 mm
|
419 mm
|
|
|
|
|
|
|
|
|
185 mm
|
185 mm
|
185 mm
|
204 mm
|
|
|
250 mm
|
250 mm
|
250 mm
|
260 mm
|
|
Weight, approx.
|
7.5 kg
|
7.5 kg
|
7.5 kg
|
13 kg
|
1) The base load current IH is based on the duty cycle for high overload applications (machine tool spindle application).
|
Product name
|
Control Unit CU240B-2
6SL3244-0BB00-1BA1
|
|
Operating voltage
|
24 V DC via the Power Module
|
|
Current consumption, max.
|
0.5 A
|
|
Protective insulation
|
PELV according to EN 50178 Protective separation from the line supply using double/reinforced insulation
|
|
Power loss
|
< 5.5 W
|
|
Analog input
|
1 differential input Switchable using DIP switch between voltage and current: -10 ... +10 V, 0/4 ... 20 mA, 10-bit resolution Analog inputs are protected against inputs in a voltage range of ± 30 V and have a common-mode voltage in the ± 15 V range
|
|
PTC/KTY interface
|
1 motor temperature sensor input, sensors that can be connected: PTC, KTY and Thermo-Click, accuracy ± 5 °C
|
|
U/f linear/square/parameterizable
|
Yes
|
|
Operator panel
|
BOP-2
|
|
Memory card
|
SINAMICS micro memory card (MMC)
|
|
PC interface
|
USB (connection via PC inverter connection kit 2)
|
|
Degree of protection
|
IP20
|
|
Signal cable cross-section
|
|
|
|
0.05 mm2 (AWG30)
|
|
|
1.5 mm2 (AWG16)
|
|
Operating temperature
|
0 ... 50 °C
|
|
Storage temperature
|
-40 ... +70 °C
|
|
Relative humidity
|
< 95 % RH, condensation not permissible
|
|
Dimensions
|
|
|
|
73 mm
|
|
|
199 mm
|
|
|
46 mm
|
|
Weight, approx.
|
0.49 kg
|
|
Product name
|
Basic Operator Panel BOP-2
|
| |
6SL3244-0AA00-4CA1
|
|
Operating temperature
|
0 ... 50 °C
|
|
|