Article?No.
|
6GK1?551-2AA00
|
|
Product-type?designation
|
CP?5512
|
|
Transmission?rate
|
|
|
Transmission?rate?at?interface?1?in?accordance?with?PROFIBUS
|
9,6 kbit/s … 12 Mbit/s
|
|
Interfaces
|
|
|
Number?of?electrical?connections?at?interface?1?in?accordance?with?PROFIBUS
|
1
|
|
Design?of?electrical?connection
|
|
- at?interface?1?in?accordance?with?PROFIBUS
|
9-pin?Sub-D?socket?(RS?485)
|
|
|
|
|
Supply?voltage,?current?consumption,?power?loss
|
|
|
Type?of?supply?voltage
|
DC
|
|
Supply?voltage?1?from?backplane?bus
|
3.3 V
|
|
Relative?symmetrical?tolerance?at?3.3?V?with?DC
|
5 %
|
|
Consumed?current?1?from?backplane?bus?with?DC?maximum
|
0,52 A
|
|
Resistive?loss
|
1.8 W
|
|
Permitted?ambient?conditions
|
|
|
Ambient?temperature
|
|
|
|
5 … 45 °C
|
|
|
-20 … +60 °C
|
|
|
-20 … +60 °C
|
|
Relative?humidity?at?25?°C?without?condensation?during?operating?maximum
|
95 %
|
|
Protection?class?IP
|
IP00
|
|
Design,?dimensions?and?weight
|
|
|
Module?format
|
PC?card?Type?II?CardBus?(32?bit)
|
|
Width
|
86 mm
|
|
Height
|
5 mm
|
|
Depth
|
54 mm
|
|
Net?weight
|
0.13 kg
|
|
Product?properties,?functions,?components?general
|
|
|
Number?of?plug-in?cards?in?the?same?design?can?be?plugged?in?per?PC?station
|
1
|
|
Number?of?modules?note
|
-
|
|
Performance?data
|
|
|
Performance?data?open?communication
|
|
|
Software?for?open?communication?by?means?of?SEND/RECEIVE?required
|
Yes,?SOFTNET-PB?DP?/?SOFTNET-PB?DP?Slave?/?SOFTNET-PB?S7
|
|
Number?of?possible?connections?for?open?communication?by?means?of?SEND/RECEIVE?maximum
|
50
|
|
Performance?data?PROFIBUS?DP
|
|
|
Software?for?DP?master?function?required
|
Yes,?SOFTNET-PB?DP
|
|
Service?as?DP?master
|
|
|
|
Yes
|
|
|
No
|
|
|
No
|
|
Number?of?DP?slaves?on?DP?master?usable
|
64
|
|
Amount?of?data
|
|
- of?the?address?area?of?the?inputs?as?DP?master?overall
|
7 808 byte
|
- of?the?address?area?of?the?outputs?as?DP?master?overall
|
7 808 byte
|
- of?the?address?area?of?the?inputs?per?DP?slave
|
244 byte
|
- of?the?address?area?of?the?outputs?per?DP?slave
|
244 byte
|
- of?the?address?area?of?the?diagnostic?data?per?DP?slave
|
244 byte
|
|
Software?for?DP?slave?function?required
|
Yes,?SOFTNET-PB?DP?slave
|
|
Service?as?DP?slave
|
|
|
|
Yes
|
|
|
No
|
|
Amount?of?data
|
|
- of?the?address?area?of?the?inputs?as?DP?slave?overall
|
122 byte
|
- of?the?address?area?of?the?outputs?as?DP?slave?overall
|
122 byte
|
|
Performance?data?S7?communication
|
|
|
Software?for?S7?communication?required
|
Yes,?SOFTNET-PB?S7
|
|
Number?of?possible?connections?for?S7/PG?communication?maximum
|
8
|
|
Performance?data?multi-protocol?mode
|
|
|
Number?of?configurable?connections?per?PC?station
|
207
|
|
Product?functions?management,?configuration
|
|
|
Configuration?software?required
|
|
|
Product?functions?Diagnosis
|
|
|
Product?function?Port?diagnostics
|
Yes
|
|
Standards,?specifications,?approvals
|
|
|
Standard
|
|
|
|
2004/108/EC
|
|
|
CAN/CSA?C22.2?&?UL?60950-1
|
|
|
EN?61000-6-3,?EN?61000-6-4
|
- for?interference?immunity
|
EN?61000-6-1,?EN?61000-6-2
|
|
Verification?of?suitability
|
|
|
|
Yes
|
|
|
Yes
|