Output
|
|
|
Output signal
|
0 ... 20 mA or 4 ... 20 mA
|
|
Load
|
Max. 750 Ω
|
|
Voltage measurement
|
Linear (square-rooting in transmitter if necessary)
|
|
Electrical isolation
|
Between power supply and input/ output
|
|
Measuring accuracy
|
|
|
Conformity error (in addition to transmitter)
|
≤ 0.15 % of set span
|
|
Influence of ambient temperature
|
≤ 0.1 % per 10 K
|
|
Power supply effect
|
≤ 0.1 % per 10 % change in voltage or frequency
|
|
Load effect
|
≤ 0.1 % per 100 % change
|
|
Rated conditions
|
|
|
Ambient temperature
|
-20 ... +80 °C (-4 ... +176 °F)
|
|
Storage temperature
|
-50 ... +85 °C (-58 ... +185 °F)
|
|
Degree of protection
|
IP54 to EN 60529
|
|
Electromagnetic compatibility (EMC)
|
EN 50081, EN 50082
|
|
Structural design
|
|
|
Dimensions (W x H x D) in mm (inch)
|
80 x 120 x 60 (3.15 x 4.72 x 2.36)
|
|
Electrical connection
|
Screw terminals (Pg 13.5 cable inlet) or Han 7D / Han 8U plug
|
|
Power supply
|
|
|
Supply voltage
|
230 V AC (-10 ... +6 %, 47 ... 63 Hz, approx. 6 VA) or
24 V AC/DC (24 V AC ± 10 %, 47 ... 63 Hz, approx. 3 VA)
|
|
Permissible ripple (within the specified limits)
|
Approx. 2.5 V pp
|