Input | В |
Measured variable | Gauge pressure (flush-mounted) |
| В | HART | PROFIBUS PA/ FOUNDATION Fieldbus | В | В |
Span (infinitely adjustable) or nominal measuring range and max. permissible test pressure | Span | Nominal measuring range | Max. perm. operating pressure MAWP (PS) | Max. permissible test pressure |
0.01 ... 1 bar 1 ... 100 kPa 0.15 ... 14.5 psi | 1В bar 100 kPa 14.5В psi | 4В bar 400 kPa 58В psi | 6В bar 600 kPa 87В psi |
0.04В ...В 4В bar 4 ... 400 kPa 0.58В ...В 58В psi | 4В bar 400 kPa 58В psi | 7В bar 0.71 MPa 102В psi | 10В bar 1 MPa 145В psi |
0.16В ...В 16В bar 16 ... 1600 kPa 2.3В ...В 232В psi | 16В bar 1600 kPa 232В psi | 21В bar 2.1 MPa 305В psi | 32В bar 3.2 MPa 464В psi |
Lower measuring limit (for PMC Style Minibolt no span < 500 mbar adjustable) | 100 mbar a/10 kPa a/1.45 psia |
Upper measuring limit | 100 % of max. span |
Output | HART | PROFIBUS PA/ FOUNDATION Fieldbus |
Output signal | 4В ...В 20 mA | Digital PROFIBUS PA signal |
- Lower limit (infinitely adjustable)
| 3.55 mA, factory preset to 3.84 mA | - |
- Upper limit (infinitely adjustable)
| 23 mA, factory preset to 20.5 mA or optionally set to 22.0 mA | - |
Load | В | В |
| RB ≤ (UH - 10.5 V)/0.023 A in Ω, UH: Power supply in V | - |
| RB = 230 ... 500 О© (SIMATIC PDM) or RB = 230 ... 1100 О© (HART Communicator) | - |
Physical bus | - | IEC 61158-2 |
Protection against polarity reversal | Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. |
Electrical damping (step width 0.1 s) | Set to 2 s (0 ... 100 s) |
Measuring accuracy | According to IEC 60770-1 |
Reference conditions | - Rising characteristic curve
- Start of scale 0 bar
- Seal diaphragm stainless steel
- Silicone oil filling
- Room temperature (25В В°C (77В В°F))
|
Measuring span ratio r (spread, Turn-Down) | r = maximum measuring span/set measuring span or nominal measuring range |
Error in measurement at limit setting including hysteresis and reproducibility | В |
| В |
| ≤ 0.075 % |
| ≤ (0.005 · r + 0.05) % |
Effect of ambient temperature | ≤ (0.08 · r + 0.16) % |
Long-term stability (temperature change ±30 °C (±54 °F)) | ≤ (0.25 · r) % in 5 years |
Influence of mounting position | ≤ 0.1 mbar/0.01 kPa/0.00145 psi per 10° incline (zero point correction is possible with position error compensation) |
Effect of auxiliary power (in percent per voltage change) | 0.005 % per 1 V |
Measured-value resolution for PROFIBUS PA and FOUNDATION Fieldbus | 3В В·В 10-5 of nominal measuring range |
Rated conditions | В |
Installation conditions | В |
Ambient temperature | Observe the temperature class in areas subject to explosion hazard. |
- Measuring cell with silicone oil
| -40В ...В +85В В°C (-40В ...В +185В В°F) |
| -30В ...В +85В В°C (-22В ...В +185В В°F) |
| -50В ...В +85В В°C (-58В ...В +185В В°F) |
Climatic class | В |
Condensation | Relative humidity 0 ... 100 % Condensation permissible, suitable for use in the tropics |
Degree of protection acc. to ENВ 60529 | IP65, IP68, NEMA 4X, enclosure cleaning, resistant to lyes, steam to 150 В°C (302 В°F) |
Electromagnetic compatibility | В |
- Emitted interference and interference immunity
| Acc. to EN 61326 and NAMUR NE 21 |
Process conditions | В |
Temperature of medium | В |
- Measuring cell with silicone oil
| -40В ...В +100В В°C (-40В ...В +212В В°F) |
Design | В |
Weight (without options) | Approx. 1 kg (2.2 lb) |
Enclosure material | Stainless steel, mat. no. 1.4301/304 |
Material of parts in contact with the medium | В |
| Hastelloy C276, mat. no. 2.4819 |
| Silicone oil |
Surface quality touched-by-media | Ra-values ≤ 0.8 µm (32 µ-inch)/welds Ra ≤ 1.6 µm (64 µ-inch) |
Power supply UH | HART | PROFIBUS PA/ FOUNDATION Fieldbus |
Terminal voltage on transmitter | 10.5 ... 42 V DC for intrinsically safe operation: 10.5В ...В 30В V DC | - |
Auxiliary power | - | Bus-powered |
Separate supply voltage | - | Not necessary |
Bus voltage | В | В |
| - | 9В ...В 32В V |
- With intrinsically-safe operation
| - | 9 ... 24 V |
Current consumption | В | В |
| - | 12.5 mA |
- Start-up current ≤ basic current
| - | Yes |
- Max. fault current in the event of a fault
| - | 15.5 mA |
Fault disconnection electronics (FDE) available | - | Yes |
Certificates and approvals | HART | PROFIBUS PA/ FOUNDATION Fieldbus |
Classification according to pressure equipment directive (PEDВ 2014/68/EU) | For gases of fluid group 1 and liquids of fluid groupВ 1; complies with requirements of ArticleВ 4, ParagraphВ 3 (sound engineering practice) |
Explosion protection | В |
Intrinsic safety "i" | PTB 05 ATEX 2048 |
Marking | II 1/2 G Ex ia llC/llB T4/T5/T6 Ga/Gb |
Permissible ambient temperature | В |
| -40В ...В +85В В°C (-40В ...В +185В В°F) |
| -40В ...В +70В В°C (-40В ...В +158В В°F) |
| -40В ...В +60В В°C (-40В ...В +140В В°F) |
Wiring | To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 О© | To certified intrinsically-safe circuits with peak values: FISCO supply unit: Ui = 17.5В V, Ii = 380В mA, Pi = 5.32В W Linear barrier: Ui = 24В V, Ii = 250В mA, Pi = 1.2В W |
Effective internal capacitance | Ci = 6В nF | Ci = 1.1В nF |
Effective internal inductance | Li = 0.4 mH | Li ≤ 7 μH |
Explosion protection to FM for USA and Canada (cFMUS) | В |
- Identification (DIP) or (IS); (NI)
| Certificate of Compliance 3025099 CLВ I, DIVВ 1, GP ABCD T4 ... T6; CLВ II, DIVВ 1, GPВ EFG; CLВ III; CLВ I, ZNВ 0/1 AEx ia IIC T4 ... T6; CLВ I, DIVВ 2, GPВ ABCD T4 ... T6; CLВ II, DIVВ 2, GPВ FG; CLВ III |
- Identification (DIP) or (IS)
| Certificate of Compliance 3025099C CLВ I, DIVВ 1, GP ABCD T4 ... T6; CLВ II, DIVВ 1, GPВ EFG; CLВ III; Ex ia IIC T4 ... T6; CLВ I, DIVВ 2, GPВ ABCD T4 ... T6; CLВ II, DIVВ 2, GPВ FG; CLВ III |