6ES7132-7HB00-0AB0Цена на сайте указана розничная в ЕВРО без учета НДС. Для уточнения цены и размера предоставляемой скидки - звоните или присылайте заявки | Заказной номер | Вес | PG | Описание продукта | Цена | | 6ES7132-7HB00-0AB0 | 0.35 | 287 | SIMATIC DP, ЭЛЕКТРОННЫЙ СУБМОДУЛЬ РЕЛЕЙНЫХ ВЫХОДОВ, ДЛЯ ET200ISP, 2DO RELAY UC60V / 2A | По запросу |
п»їDigital input modules- 8-channel digital input module DI NAMUR EEx i, for evaluation of NAMUR sensors, connected and non-connected contacts, as well as for use as counter or frequency meter
Parameterizable connections:- NAMUR sensor on/off
- NAMUR changeover contact
- Single contact connected (mechanical NO contact)
- Changeover contact connected (mechanical changeover contact)
- Single contact non-connected (mechanical NO contact with single contact)
- Changeover contact non-connected (mechanical changeover contact)
- Counting function: optional use of 2В channels for recording counter pulses or for frequency measurement
- Short-circuit and wire break monitoring
Digital output modules- 4-channel digital output modules DO EEx i, 23.1В V DC/20В mA, 17.4В V DC/27В mA , 17.4В V DC/40В mA or 25.5В V DC/22В mA, with external actuator switch-off via High or Low signal (H/L switch-off)
- Load-free switching of outputs via external intrinsically-safe signal
- Power boosting through parallel connection of two outputs for one actuator with 4В DO 17.4В V DC/27В mA or 4 DO 17.4 V DC/40В mA
- Short-circuit and wire break monitoring
- 2-channel digital output module DO Relay EExВ e, e.g. for switching solenoid valves, DC contactors or signaling lamps
- Can be plugged onto TM-RM/RM terminal module
- Output current up to 2В A with 60В V UC for each of the two relay outputs
- Installation up to Ex zone 1
- Intrinsically-safe and non-intrinsically-safe signals can be mixed in a station
Extra functionsActuator shutdown function of the 4В DO EExВ i modules The 4В DOВ EExВ i modules are equipped with a shutdown function. This permits implementation of an external switch-off independent of the automation system (controller). As soon as the intrinsically-safe switch-off signal (High or Low) is present at the actuator switch-off input of the electronics module, its outputs are deactivated. You can also combine several DO modules into a switch-off group. The intrinsically-safe power supply for the switch-off device is either via the watchdog module or a separate intrinsically-safe source.
|
|