3RV2011-1JA10

Öåíà íà ñàéòå óêàçàíà ðîçíè÷íàÿ â ÅÂÐÎ áåç ó÷åòà ÍÄÑ.
Äëÿ óòî÷íåíèÿ öåíû è ðàçìåðà ïðåäîñòàâëÿåìîé ñêèäêè - çâîíèòå èëè ïðèñûëàéòå çàÿâêè

Çàêàçíîé íîìåðÂåñPGÎïèñàíèå ïðîäóêòàÖåíà
3RV2011-1JA100.3441EÀÂÒÎÌÀÒÈ×ÅÑÊÈÉ ÂÛÊËÞ×ÀÒÅËÜ ÄËß ÇÀÙÈÒÛ ÝËÅÊÒÐÎÄÂÈÃÀÒÅËß, ÒÈÏÎÐÀÇÌÅÐ S00, ÊËÀÑÑ 10, ÐÅÃÓËÈÐÎÂÊÀ ÐÀÑÖÅÏÈÒÅËß ÏÅÐÅÃÐÓÇÊÈ 7...10A, ÓÑÒÀÂÊÀ ÐÀÑÖÅÏÈÒÅËß ÒÎÊΠÊÇ ÌÃÍÎÂÅÍÍÎÃÎ ÄÅÉÑÒÂÈß 130A, ÂÈÍÒÎÂÛÅ ÊËÅÌÌÛ, ÑÒÀÍÄÀÐÒÍÀß ÊÎÌÌÓÒÀÖÈÎÍÍÀß ÑÒÎÉÊÎÑÒÜÏî çàïðîñó


Selection and ordering data

The following table lists recommendations for additional line-side components, such as fuses and circuit breakers.

Note for use in compliance with IEC standards:

Type 3NA3 fuses and type 3RV circuit breakers are recommended for European countries. The values in the table take into account the overload capability of the inverter.

Notes for use in compliance with UL regulations:

Fuses for use in North America must be UL-certified, class J, T, CC, G or CF fuses with a rated voltage of 600 V AC.

Short Circuit Current Rating (SCCR)
according to UL

Applies to industrial control panel installations to NEC Article 409 or UL 508A.

  • SINAMICS G120C: 100 kA (the value depends on the fuses and circuit breakers used)

Notes regarding installations in Canada:

Overvoltage protection devices in accordance with overvoltage category III and with the following ratings must be connected on the line side of the inverter:

  • Rated voltage 480 V (phase-phase) and 480 V (phase-ground)
  • Voltage limit 4 kV (phase-phase) and 6 kV (phase-ground)

All overvoltage protection devices used must comply with Canadian standards for industrial installations.

Further information, particularly regarding use in accordance with UL guidelines, is available at
https://support.industry.siemens.com/cs/document/109478990

Additional information about the listed fuses and circuit breakers is available in the Catalogs LV 10, IC 10 and IC 10 AO as well as in the Industry Mall.

Rated power

SINAMICS G120C

IEC-compliant

UL/cUL-compliant

 

 

 

Fuse

Circuit breaker

Fuse type
Rated voltage 600 V AC

 

 

 

Current

3NA3

2NE1

 

 

Current

kW

hp

Type 6SL3210-...

Frame size

A

Article No.

Article No.

Article No.

Class

A

Line voltage 380 ... 480 V 3 AC

0.55

0.75

1KE11-8..2

FSAA

10

3NA3803

–

3RV2011-1JA10

J, T, CC, G, CF

10

0.75

1

1KE12-3..2

1.1

1.5

1KE13-2..2

1.5

2

1KE14-3..2

2.2

3

1KE15-8..2

3

4

1KE17-5..1

FSA

16

3NA3805

–

3RV2011-4AA10

J, T, CC, G, CF

15

4

5

1KE18-8..1

5.5

7.5

1KE21-3..1

FSB

32

3NA3812

–

3RV2021-4EA10

J, T, CC, G, CF

35

7.5

10

1KE21-7..1

11

15

1KE22-6..1

FSC

63

3NA3822

–

3RV1041-4JA10

J, T, CC, G, CF

60

15

20

1KE23-2..1

18.5

25

1KE23-8..1

22

30

1KE24-4.F1

FSD

80

3NA3824

3NE1820-0

3RV2031-4WA10

J, T, CC, G, CF

70

30

40

1KE26-0.F1

FSD

100

3NA3830

3NE1021-0

3RV1041-4LA10

J, T, CC, G, CF

90

37

50

1KE27-0.F1

3RV1041-4MA10

J, T, CC, G, CF

100

45

60

1KE28-4.F1

FSD

125

3NA3832

3NE1022-0

–

J, T, CC, G, CF

125

55

75

1KE31-1.F1

FSE

160

3NA3836

3NE1224-0

–

J, T, CC, G, CF

150

75

100

1KE31-4.F1

FSF

200

3NA3140

3NE1225-0

–

J, T, CC, G, CF

200

90

125

1KE31-7.F1

FSF

250

3NA3142

3NE1277-0

–

J, T, CC, G, CF

250

110

150

1KE32-1.F1

FSF

315

3NA3250

3NE1230-0

–

J, T, CC, G, CF

300

132

200

1KE32-4.F1

FSF

350

3NA3252

3NE1331-0

–

J, T, CC, G, CF

350